BA HERCS, Model VIG 2, all in one, self-
contained non electric control valve that has been developed for
domestic hot water (DHW) production in systems with or without hot water
service tanks and charging systems for hot water service tanks. The
controller is used for temperature controlling with steam or hot water
up to 235° F (110° C)
The temperature controller is a
self-acting proportional controller for temperature control and
monitoring, operate according to the liquid expansion principle.
The control valve combined with a
safety temperature limiter that will shut down the valve when the high
temperature set point is reached. No electric solenoid valves needed.
Valves sizes from ½” (DN 15) to 1 ½” (DN
)
Valves come with 2 DIN flanges, bolts
and gaskets.
Valves come in 2 way or 3 way
configurations.
Max pressure/ temperature:
Valve – 362 PSI (25 bar)/ up to 302° F
(150° C)
Temperature Sensor – 362 PSI (25 bar)/
347° F (175° C)
Valve Ordering Information
|
Pipe Size |
|
|
Part Number |
|
Inches |
DN |
Cv |
Kvs |
362 PSI (25 bar) |
|
1/2" |
15 |
3.5 |
4.0 |
065B2448 |
|
3/4" |
20 |
7.4 |
6.3 |
065B2449 |
|
1" |
25 |
9.4 |
8.0 |
065B2450 |
|
1 1/4" |
32 |
14.6 |
12.5 |
065B2451 |
|
1 1/2" |
40 |
18.7 |
16.0 |
065B2452 |
Technical Data
Nominal pressure: 362 PSI (25 bar)/
flanges to DIN 2501
Flow medium / Temperature Steam / max.
662° F (350° C)
Pressure balance, Stainless steel
bellow, mat. No.1.4571, Rolling diaphragmValve body material:
362 PSI (25 bar) Ductile iron
EN-GJS-400-18-LT (GGG-40.3)
Cone material: Stainless steel, mat. No.
1.4021 No. 1.4313
Seat material: Stainless steel, mat. No.
1.4021

Mode of Operation
The controllers are
proportional controllers
and the valves are
pressure-balanced.
Safety Temperature
Monitor (STW)
Function STW
When reaching the set
limit temperature at the temperature
sensor (5), the safety temperature monitor
interrupts energy supply by closing the valve
(1). As soon as the temperature at the
temperature sensor drops, the valve is
opening automatically. The limit temperature is
adjusted at the setpoint
adjuster (3.1) with
temperature scale. The setpoint adjuster can
be sealed.
Extended Safety
STW
If there is a leakage
in the temperature
sensor, the
connection pipe, or the
thermostat, the valve
is closed by a pressure
spring in the safety
thermostat.
Physical
Function Principle STW
The safety thermostat
(3) operates in
accordance with the
liquid expansion
principle. The
temperature sensor, the
connection pipe, and
the working element are
filled with liquid.
As the temperature at the
temperature sensor
rises, the liquid expands,
the working stem of
the thermostat is pressed
out and the valve VIG
2 is closed.

Mounting
A strainer must be
installed in front of the
controller: Nom.
diameter ½” & ¾” (DN 15 – 25)
0.5 mm Nom.
diameter 1 ¼” & 1 ½” (DN 32 – 40)
Strainer mesh size
0.8 mm The controller may
be installed in any position. |



|
Pipe Size |
L2 |
H1 |
Weight |
|
Inches |
DN |
Inches |
mm |
Inches |
mm |
Pound |
kg |
|
1/2' |
15 |
5.1 |
130 |
1.3 |
35 |
5.5 |
2.5 |
|
3/4" |
20 |
5.9 |
150 |
1.4 |
36 |
6.6 |
3.0 |
|
1" |
25 |
6.2 |
160 |
1.5 |
37 |
7.7 |
3.5 |
|
1 1/4" |
32 |
7.1 |
180 |
2.2 |
57 |
14.3 |
6.5 |
|
1 1/2" |
40 |
7.8 |
200 |
2.4 |
62 |
19.8 |
9.0 |
Valve Body
Construction
1
Valve VIG 2
2
Trim
2.1
Valve plug
3
Safety thermostat STIW
3.1
Setpoint adjuster with
safety
bore
4
Thermostat AIT
4.1
Setpoint adjuster with
safety
bore
5
Temperature sensor
6
Immersion pocket
7
Combination piece KI1
Temperature
Controller (TR)
Function TR
The temperature of a
medium is controlled by the temperature
controller (TR) in accordance with the adjusted
setpoint. The setpoint is adjusted by turning
the setpoint adjuster(4.1). The setpoint
adjuster may be sealed.
Physical
Function Principle TR
The thermostat AIT(4)
operates in accordance with the adsorption
principle. A pressure is generated in the
temperature sensor (5) which is proportional
to the medium temperature. The
pressure is transferred via the connection pipe
to the metal bellows of the thermostat. The
stem of the thermostat is pressed out and the
valve VIG2 is closed.
|
Type |
Set
|
points |
Mounting |
Part
|
|
AIT |
°F |
°C |
|
Number |
|
for
valves |
68 –
158 |
20 – 70 |
6.7” |
065 –
4135 |
|
½”,
¾”, 1” |
104 –
194 |
40 – 90 |
(170
mm) |
065 –
4396 |
|
DIN 15
– 25 |
104 –
230 |
40 –
110 |
R 1/2 |
065 –
4397 |
|
For
valves |
95 –
158 |
35 – 70 |
8.3” |
065 –
4139 |
|
1 ¼” ,
1 ½” |
104 –
194 |
40 – 90 |
(210mm) |
065 –
4140 |
|
DIN 32,
40 |
140 –
230 |
60 –
110 |
R 3/4 |
065 –
4141 |
|
STIW |
50 –
167 |
30 –
110 |
Safety
Limiter |
065 –
4142 |
|
All
Valves |
86 –
203 |
20 – 75 |
8.3”
(210mm) |
065 –
4143 |
|
|
104 –
230 |
40 – 95 |
R 3/4 |
065 –
4144 |

The sensor must be
immersed into the medium by its full
length. Select the location of installation in
such a way that the highest temperature of the
medium is measured directly and without
any delay. The setpoint
adjusters of the thermostats STIW, AIT may be
sealed. For temperatures higher than 248°F
(120 °C), the safety temperature monitor must be secured with a seal.
|