Specification:
Three-way
mixing valve ”Tri-M” 145 PSIG (PN 10 Bar) up to 248°F (120 °C), for
short periods up to 284°F (140 °C).
Bronze
body. Connection thread M 30 x 1.5. Steady or two point control with
temperature controllers or electrothermal electric actuators. Three-way
mixing valves ”Tri-M” are supplied with collar nuts for the connection
of either weldable
tailpipes
made of steel or solder- or screwed tailpipes made of brass.
Accessories sets:
Weldable
tailpipes DN...3/4” (20), 1” (25), 1 ½” (40 mm)
Solder
tailpipes ½” (15), ¾” (18), 1” (22), 1 ¼” (35), 1 ½” (42 mm)
Screwed
tailpipes 1/2”, 3/4”, 1”, 11/4”, 11/2” (Male Threads)
Function:
Three-way
mixing valves ”Tri-M” have two inlet ports and one outlet port.
Depending on the position of the valve disc, the cold and hot water is
mixed. For commercial two point controls, the electrothermal actuator is
used, with the straight port being opened with current ”off” and the
port opposite the actuator being closed. Reversed action with the
current ”on”. The working procedure of the actuators can be reversed,
i.e. straight port closed with current ”off”. Pressure waves are not
produced during changeover and the volume of flow remains constant. Our
actuators have an expansion type working element which is heated
electrically. When using a steady control, Our temperature controllers
with immersion sensor
or our
temperature controllers with contact sensor are used. These are
proportional controllers working without auxiliary energy and allowing
intermediate positions. With the temperature at the sensor rising, the
straight port is opened and the angle port is closed.

Model:
Valve body made of
corrosion-resistant bronze, inner parts
made of brass and
stainless steel, EPDM washers.
Application:
Mixing and changing over
of the flow in bivalent heating systems
or hot water storage
cylinders, e.g. solar heating and
heat pump installations.
Temperature of fluid up to 248°F
(120°
C), for short periods up to 284°F
(140 °C).
Permissible pressure
difference: ¾” 750 mbar, 1” 500
mbar, 1 ½” 200 mbar
(tight closing in final positions of the
valve disc).
Max. working pressure:
145 psig (10 bar)

Examples of installation


Increase of return
temperature for solid fuel boilers.
The desired return
temperature is set at the temperature
controller. With the
return temperature increasing, the
bypass between the supply
and return pipe is throttled and
vice versa.
Use in a bivalent
heating system
With a sufficient
duration of sunshine, the solar heating
system is in operation.
Is this duration not sufficient, the
oil- or gas fired boiler
is added to the heating circuit by
means of the three-way
mixing valve. A constant temperature
of domestic water is thus
guaranteed.

|